400V SPF Series(2.2KW~18.5KW)

Model

SPF-2.2K

SPF-4.0K

SPF-5.5K

SPF-7.5K

SPF-11K

SPF-15K

SPF-18.5K

Applicable Motor Capacity

2.2kW

4.0kW

5.5kW

7.5kW

11kW

15kW

18.5kW

Output

Rated Capacity (*1)

3.8kVA

6.2kVA

8.7kVA

11.8kVA

17.3kVA

22.2kVA

26.3kVA

Rated Current (*2)

5.5A

8.9A

12.6A

16.4A

24A

32A

38A

Overload Current Rating

120% 1 min

Rated Output Voltage

3¦µ, 380V at 50Hz, 400V at 50Hz, 460V at 60Hz

Input

Rated Voltage and Frequency

3¦µ, 380V to 460V at 50Hz or 60Hz

Allowable Fluctuation

Voltage:-15%, +10%   Frequency:¡À5% Voltage imbalance: 3%max

Power Supply Impedance

1% or more (Use the optional reactor if less than 1%)

Protective Structure

Totally enclosed£¨IP20£©

Cooling Method

Forced air cooling

Weight

4kg

4kg

4.5kg

6.5kg

6.5kg

7kg

10kg

Control Function

Control Method

V/f control or sensorless vector control

High-Frequency Carrier

Sine wave PWM (carrier frequency: 1 to 14 kHz) (*3)

Output Frequency Range

0.05 to 200 Hz (starting frequency: 0.05 to 20 Hz variable) (*4)

Frequency Setting Resolution

Digital Setting

0.01 Hz (0.05 to 200 Hz)

Analog Setting

0.1% (10 bits for 0 to 10 V, 4 to 20 mA), 0.2% (9 bits for 0 to 5 V) for maximum output frequency

Frequency Accuracy

Digital Setting

¡À0.01% of the output frequency (at -10 to +40¡ãC)

Analog Setting

¡À0.2% of the maximum output frequency (at 25 ¡À10¡ãC) (*5)

DC Braking

Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)

Additional Functions

Restart after momentary power failure, flying start, multi-speed operation, frequency jump, auto alarm recovery,

PID control operation, simple scheduled operation, energy-saving operation, torque limiter (for sensorless vector control only)

Operation Function

Start/Stop Setting

Operation panel, serial communication (RS485, RS232C), control circuit terminals

Frequency Command Setting

Digital Setting

Operation panel, serial communication (RS485, RS232C), step setting from terminal board

Analog Setting

2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA, variable resistor (5 kΩ, 0.3 W or more)

Input Signals

Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run stop/alarm reset, emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only)

[Digital input; 8 channels (arbitrary allocation)] [Analog input; 1 channel for voltage, 1 channel for current and voltage]

Output Signals

Contact Output

Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A)

Monitor Signal

Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach

[Open-collector output: 3 channels (arbitrary allocation), Analog output: 2 channels]

LED Display

Frequency, output current, synchronous rotation, load factor, output voltage, pressure, line speed (no units), operating, alarm

Serial Communication I/F

RS485, RS232C

Function Extension

Software upgrade by RS232C serial communication supported

External Power Supply Output

24V DC, 150 mA (control terminal)

Protection Functions

Current limiting, overcurrent shutoff, motor overload, external thermal alarm, undervoltage, overvoltage, momentary power failure, fin overheat, missing phase

Warning Functions

Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins

Environment

Ambient Temperature

-10 to +40¡ãC (Remove the top ventilation cover of the SPF-5.5K or a lower model at temperatures of +30¡ãC or higher)

Storage Temperature

-20 to +65¡ãC (*6)

Ambient Humidity

90%RH or less (with no condensation)

Operating Environment

Indoor at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust)

*1 Rated capacity at the output voltage of 400 V
*2 Rated current should be reduced according to outout power when input voltage is 400 VAC or higher.
*3 The maximum carrier frequency varies depending on the capacity of the inverter and the operating status.
*4 The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
*5 The maximum output frequency is at 5 V, 10 V, and 20 mA.
*6 This temperature is for short periods, such as during transportation.