| Model |
SPF-2.2K |
SPF-4.0K |
SPF-5.5K |
SPF-7.5K |
SPF-11K |
SPF-15K |
SPF-18.5K |
| Applicable Motor Capacity |
2.2kW |
4.0kW |
5.5kW |
7.5kW |
11kW |
15kW |
18.5kW |
| Output |
Rated Capacity (*1) |
3.8kVA |
6.2kVA |
8.7kVA |
11.8kVA |
17.3kVA |
22.2kVA |
26.3kVA |
| Rated Current (*2) |
5.5A |
8.9A |
12.6A |
16.4A |
24A |
32A |
38A |
| Overload Current Rating |
120% 1 min |
| Rated Output Voltage |
3¦µ, 380V at 50Hz, 400V at 50Hz, 460V at 60Hz |
| Input |
Rated Voltage and Frequency |
3¦µ, 380V to 460V at 50Hz or 60Hz |
| Allowable Fluctuation |
Voltage:-15%, +10% Frequency:¡À5% Voltage imbalance: 3%max |
| Power Supply Impedance |
1% or more (Use the optional reactor if less than 1%) |
| Protective Structure |
Totally enclosed£¨IP20£© |
| Cooling Method |
Forced air cooling |
| Weight |
4kg |
4kg |
4.5kg |
6.5kg |
6.5kg |
7kg |
10kg |
| Control Function |
Control Method |
V/f control or sensorless vector control |
| High-Frequency Carrier |
Sine wave PWM (carrier frequency: 1 to 14 kHz) (*3) |
| Output Frequency Range |
0.05 to 200 Hz (starting frequency: 0.05 to 20 Hz variable) (*4) |
| Frequency Setting Resolution |
Digital Setting |
0.01 Hz (0.05 to 200 Hz) |
| Analog Setting |
0.1% (10 bits for 0 to 10 V, 4 to 20 mA),
0.2% (9 bits for 0 to 5 V) for maximum output frequency |
| Frequency Accuracy |
Digital Setting |
¡À0.01% of the output frequency (at -10 to +40¡ãC) |
| Analog Setting |
¡À0.2% of the maximum output frequency (at 25 ¡À10¡ãC) (*5) |
| DC Braking |
Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking
force (1 to 10 steps) |
| Additional Functions |
Restart after momentary power failure, flying start, multi-speed operation,
frequency jump, auto alarm recovery,
PID control operation, simple scheduled operation, energy-saving operation,
torque limiter (for sensorless
vector control only) |
| Operation Function |
Start/Stop Setting |
Operation panel, serial communication (RS485, RS232C), control circuit terminals |
| Frequency Command Setting |
Digital Setting |
Operation panel, serial communication (RS485, RS232C), step setting from terminal board |
| Analog Setting |
2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA,
variable resistor (5 kΩ, 0.3 W or more) |
| Input Signals |
Frequency command, forward run command, reverse run command, acceleration/deceleration
time setting, free-run stop/alarm reset, emergency stop,
jogging selection, step frequency setting, operation signal
hold, torque limiter (sensorless
vector control only)
[Digital input; 8 channels (arbitrary allocation)] [Analog input; 1
channel for voltage, 1 channel for current and voltage] |
| Output Signals |
Contact Output |
Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A) |
| Monitor Signal |
Operating, frequency matching, overload alarm, undervoltage,
overvoltage, frequency approach
[Open-collector output: 3 channels (arbitrary allocation), Analog output:
2 channels] |
| LED Display |
Frequency, output current, synchronous rotation, load factor, output
voltage, pressure, line speed (no units), operating, alarm |
| Serial Communication I/F |
RS485, RS232C |
| Function Extension |
Software upgrade by RS232C serial communication
supported |
| External Power Supply Output |
24V DC, 150 mA (control terminal) |
| Protection Functions |
Current limiting, overcurrent shutoff, motor
overload, external thermal alarm, undervoltage,
overvoltage, momentary power failure,
fin overheat, missing phase |
| Warning Functions |
Overvoltage prevention, current limiting during
acceleration/deceleration, brake resistor overheat, overload,
overheating of radiator fins |
| Environment |
Ambient Temperature |
-10 to +40¡ãC (Remove the top ventilation
cover of the SPF-5.5K or a lower model at temperatures of
+30¡ãC or higher) |
| Storage Temperature |
-20 to +65¡ãC (*6) |
| Ambient Humidity |
90%RH or less (with no condensation) |
| Operating Environment |
Indoor at 1,000 m or lower altitude (No
direct sunlight, corrosive or inflammable gases, oil mist,
or dust) |
|
|
|
|
|
|
|
|
|
|
|
|
|
*1 Rated capacity at the output voltage of 400 V
*2 Rated current should be reduced according to outout power when
input voltage is 400 VAC or higher.
*3 The maximum carrier frequency varies depending on the capacity
of the inverter and the operating status.
*4 The frequency setting range for sensorless vector control is 1
to 130 Hz for a four-pole motor (depends on the number of poles).
*5 The maximum output frequency is at 5 V, 10 V, and 20 mA.
*6 This temperature is for short periods, such as during transportation. |
|